Specifications:
Test specifications:
The accuracy specification for the display range is defined as ±(%reading + digit counts) at 23 °C ±5 °C, ≤75% RH.
Between 0 °C and 18 °C and between 28 °C and 40 °C, accuracy specifications may degrade by 0.1 x (accuracy specification) per °C.
The measurement range meets the service operating errors specified in EN61557-1: 1997,
EN61557-2: 1997, EN61557-4: 1997, EN61557-6: 1997, DIN VDE0404-2.
Power-on test:
The test indicates reversed L-N, missing PE, and measures the mains voltage and frequency.
Display range: 90 V to 264 V
Accuracy at 50 Hz: ±(2% + 3 counts)
Resolution: 0.1 V
Input impedance: > 1 MΩ // 2.2 nF
Maximum input mains voltage: 264 V
Earth bond test (Rpe):
Display Range: 0 to 19.99 Ω
Accuracy (after bond test zeroing):±(5% + 4 counts)
Resolution: 0.01 Ω
Test current:
200 mA AC -0% +40% into 1.99 Ω
10 A AC ±20% into 25 mΩ at 230 V
Open circuit voltage: > 4 V AC, < 24 V AC
Bond test zeroing: can subtract up to 1.99 Ω
Insulation test (Riso):
Display range: 0 to 299 MΩ
Accuracy: ±(5% + 2 counts) from 0.1 to 300 MΩ
Resolution:
0.01 MΩ (0 to 19.99 MΩ)
0.1 MΩ (20 to 199.9 MΩ)
1 MΩ (200 to 299 MΩ)
Test voltage: 500 V DC -0% + 25% at 500 kΩ load or 250 V dc -0% +25% at 250 kΩ load
Test current: > 1 mA at 500 kΩ load, < 15 mA at 0 Ω
Auto discharge time: < 0.5 s for 1 μF
Max. capacitive load: Operational up to 1 μF
Touch current test:
Display range: 0 to 1.99 mA AC
Accuracy: ±(4% + 2 counts)
Resolution: 0.01 mA
Internal resistance (via probe): 2 kΩ
Measuring method: Probe*
Substitute leakage current test:
Display range: 0 to 19.99 mA AC
Accuracy: ±(2.5% + 3 counts)
Resolution: 0.01 mA
Test Voltage: 100 V AC ±20%
Load/leakage test: load current:
Display range: 0 A to 13 A
Accuracy: ±(4% + 2 counts)
Resolution: 0.1 A*
Load/leakage test: load power:
Display range: 230 V Mains 0.0 VA to 3.2 kVA
Accuracy: ±(5% + 3 counts)
Resolution: 1 VA (0 to 999 VA), 0.1 kVA (>1.0 kVA)*
Load/leakage test: leakage current:
Display range: 0 to 19.99 mA
Accuracy: ±(4% + 4 counts)
Resolution: 0.01 mA*
PELV test:
Accuracy at 50 Hz: ±(2% + 3 counts)
Overload protection: 300 V rms
Warning threshold: 25 V rms
RCD test: trip current:
Operational error: ±10%
Nominal: 30 mA
Accuracy: ±5%
RCD test: trip time
Standard requirement: 61557 Part 6; tolerance of rated test current 0% to +10%
Operational error: ±10%
RCD type: AC general-purpose 30 mA
Display range: 310 ms
Resolution: 0.1 ms
Accuracy: 3 ms
Trip time limit at 100% (30 mA): 300 ms
Trip time limit at 500% (150 mA): 40 ms
*The appliance under test is energized at mains potential.
Environmental specifications
Operating temperature: 0 to 40 °C
Relative humidity:
Non condensing <10 °C
95% from 10 to 30 °C
75% from 30 to 40 °C
Safety specifications
Safety rating:
Complies with EN61010-1 3rd edition
CAT II, 300 V, pol 2
Mechanical and general specifications
Size (L x W x H): 200 x 275 x 114 mm
Weight: 3.13 kg
Power supply: 230 V +10% -15%, 50 Hz ±2 Hz or (6500-2 only: 110V +10% -15%,50 Hz ±2 Hz)
Power consumption (tester):
13 W typical (idle)
60 W max. during 25A Bond test
Storage:
Temperature: -10 to 60 °C
Corrosion: 70 °C @ 95% RH for 5 days max.
Operating altitude: 0 up to 2000 m
Sealing: IP-40 (enclosure), IP-20 (connectors)
EMC: Complies with EN61326-1, portable
EMI Immunity: 3 V/m